Type: | Bare |
---|---|
Conductor Type: | Stranded |
Application: | Overhead |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Aerial Bundle Cable (ABC cable) is a very innovative concept for overhead power distribution as compared to the conventional bare conductor overhead distribution system.
It provides higher level of safety and reliability, lower power losses and ultimate system economy by reducing installation, maintenance and operative cost.
Caledonian LV Aerial Bundle Cables are designed to supply 600/1000 volt aerial service for temporary service at construction sites, as a service drop (power pole to service entrance), as a secondary cable (pole to pole) or street lighting.
This over-head cable provides reinforced insulation acc. IEC 61140 and fulfill therefore Class II acc. IEC 61140. It is not flame retardant. But this could be if requested change to a flame retardant cable.
Basic design to BS 7870 / TNB Specification(IEC 60502) / HD 626 S1 / NFC 33-209 / AS/NZS 3560-1 standards
Codeword |
Size |
No. of |
Resistance |
Ampacity* |
|
DC at 20°C |
AC at 75°C |
||||
Alton |
48.69 |
7 |
0.414 |
0.492 |
143 |
Ames |
77.47 |
7 |
0.260 |
0.311 |
191 |
Azusa |
123.3 |
7 |
0.164 |
0.195 |
256 |
Anaheim |
155.4 |
7 |
0.130 |
0.155 |
296 |
Amherst |
195.7 |
7 |
0.103 |
0.123 |
342 |
Alliance |
246.9 |
7 |
0.0816 |
0.0973 |
395 |
* Based on 75°C conductor temperature, 25°C ambient temperature, in sun and wind at 2 ft/sec. |
CODE* WORD | PHASE CONDUCTOR | BARE NEUTRAL MESSENGER | WEIGHT PER 1000 FT. (LBS.) | ALLOWABLE AMPACITIES+ | |||||||
Size (AWG) | Strand- ing | Insul. Thick. (mils) | Equiv. Dia. (AWG)++ | Size (kcmil) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
6201 ALLOY REDUCED NEUTRAL-MESSENGER | |||||||||||
Artemia | 4 | 1 | 45 | 6 | 30.58 | 7 | 1110 | 135 | 135 | 115 | 90 |
Crab | 4 | 7 | 45 | 6 | 30.58 | 7 | 1110 | 143 | 143 | 115 | 90 |
Solaster | 2 | 7 | 45 | 4 | 48.69 | 7 | 1760 | 216 | 216 | 150 | 120 |
Sandcrab | 1/0 | 7 | 60 | 2 | 77.47 | 7 | 2800 | 347 | 347 | 205 | 160 |
Echinus | 1/0 | 9 | 60 | 2 | 77.47 | 7 | 2800 | 341 | 341 | 205 | 160 |
Fulgar | 3/0 | 17 | 60 | 1/0 | 123.3 | 7 | 4460 | 519 | 519 | 275 | 215 |
Arca | 4/0 | 18 | 60 | 2/0 | 155.4 | 7 | 5390 | 643 | 643 | 315 | 245 |
*Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP). +Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. ++Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201. |