Duplex AAC/ACSR Conductor Overhead Power Transmission Used XLPE Twisted ABC Power Cable

Product Details
Type: Insulated
Conductor Type: Stranded
Application: Overhead

360° Virtual Tour

Diamond Member Since 2018

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
7
Year of Establishment
2016-12-30
  • Duplex AAC/ACSR Conductor Overhead Power Transmission Used XLPE Twisted ABC Power Cable
  • Duplex AAC/ACSR Conductor Overhead Power Transmission Used XLPE Twisted ABC Power Cable
  • Duplex AAC/ACSR Conductor Overhead Power Transmission Used XLPE Twisted ABC Power Cable
  • Duplex AAC/ACSR Conductor Overhead Power Transmission Used XLPE Twisted ABC Power Cable
  • Duplex AAC/ACSR Conductor Overhead Power Transmission Used XLPE Twisted ABC Power Cable
Find Similar Products

Basic Info.

Model NO.
ABC cable
Conductor Material
Aluminum
Sheath Material
Crosslinking
Insulation Material
PE
Material Shape
Round Wire
Range of Application
LSOH
Certification
ISO9001, CE, CCC, RoHS
Brand
Xcty
Transport Package
Coil/Reel
Specification
16 sqmm
Trademark
XCTY
Origin
Guangzhou
HS Code
854492100
Production Capacity
2000000 Meters a Day

Product Description

Duplex AAC/ACSR Conductor Overhead Power Transmission Used XLPE Twisted ABC Power Cable

Application

Aerial Bundle Cable (ABC cable) is a very innovative concept for overhead power distribution as compared to the conventional bare conductor overhead distribution system.

It provides higher level of safety and reliability, lower power losses and ultimate system economy by reducing installation, maintenance and operative cost.

Caledonian LV Aerial Bundle Cables are designed to supply 600/1000 volt aerial service for temporary service at construction sites, as a service drop (power pole to service entrance), as a secondary cable (pole to pole) or street lighting.

This over-head cable provides reinforced insulation acc. IEC 61140 and fulfill therefore Class II acc. IEC 61140. It is not flame retardant. But this could be if requested change to a flame retardant cable.

Standard

Basic design to BS 7870 / TNB Specification(IEC 60502) / HD 626 S1 / NFC 33-209 / AS/NZS 3560-1 standards

Construction

   
Conductor Aluminium conductor, round stranded compressed (RM).1350 aluminum wire
Insulation XPLE compound, UV-resistant.
Core Identification 1, 2 resp. 3 raised longitudinal ribs on the surface of the cores. The surface of the neutral core should have at least 12 ribs for cross-sections up to 50 mm^2 and a minimum of 16 ribs for cores above 50 mm^2. In the case of five core bundles the surface of the protective core should be smooth.

Electrical Properties

Rated Voltage 0.6/1kV
Test Voltage 4 Veff kV
Minimum Laying Temperature -20°C
Operating Temperature -40°C~ +90°C
Maximum Short-circuit Temperature 250°C
Maximum Conductor Temperature 80°C
Minimum Bending Radius 18×OD

Construction Parameters

CODE* WORD PHASE CONDUCTOR BARE NEUTRAL MESSENGER WEIGHT PER 1000 FT.(LBS.) ALLOWABLE AMPACITIES+
Size (AWG Strand- ing Insul. Thick. (mils) Equiv. Dia. (AWG)++ Size++ (kcmil) Strand- ing Rated Strength (lbs). XLP POLY XLP POLY
6201 ALLOY NEUTRAL-MESSENGER
Minex 6 1 45 6 30.58 7 1110 101 101 85 70
Hippa 6 7 45 6 30.58 7 1110 107 107 85 70
Prawn 4 1 45 4 48.69 7 1760 152 152 115 90
Barnacle 4 7 45 4 48.69 7 1760 160 160 115 90
Shrimp 2 7 45 2 77.47 7 2800 243 243 150 120
Gammarus 1/0 7 60 1/0 123.3 7 4460 390 390 205 160
Leda 1/0 9 60 1/0 123.3 7 4460 384 384 205 160
Dungenese 2/0 7 60 2/0 155.4 7 5390 483 483 235 185
Cyclops 2/0 11 60 2/0 155.4 7 5390 474 474 235 185
Flustra 3/0 17 60 3/0 195.7 7 6790 587 587 275 215
Lepas 4/0 18 60 4/0 246.9 7 8560 728 728 315 245
 

 

*Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).

+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.

++Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201.

Duplex AAC/ACSR Conductor Overhead Power Transmission Used XLPE Twisted ABC Power Cable

CODE* WORD PHASE CONDUCTOR BARE NEUTRAL MESSENGER WEIGHT PER 1000 FT. (LBS.) ALLOWABLE AMPACITIES+
Size (AWG) Strand- ing Insul. Thick. (mils) Equiv. Dia. (AWG)++ Size (kcmil) Strand- ing Rated Strength (lbs.) XLP POLY XLP POLY
6201 ALLOY REDUCED NEUTRAL-MESSENGER
Artemia 4 1 45 6 30.58 7 1110 135 135 115 90
Crab 4 7 45 6 30.58 7 1110 143 143 115 90
Solaster 2 7 45 4 48.69 7 1760 216 216 150 120
Sandcrab 1/0 7 60 2 77.47 7 2800 347 347 205 160
Echinus 1/0 9 60 2 77.47 7 2800 341 341 205 160
Fulgar 3/0 17 60 1/0 123.3 7 4460 519 519 275 215
Arca 4/0 18 60 2/0 155.4 7 5390 643 643 315 245
 

 

*Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).

+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.

++Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201.